Ceiling Type Air Handling Unit
Ruidong Group
Availability: | |
---|---|
Quantity: | |
|
Product Description
Features:
Customizable High Quality Commercial HVAC Ceiling Type Air Handling Unit for Shopping Mall/Multiplex/Small Office
1. Double 25mm and 50mm Skin Panel, outer plate is made of high quality steel sheet, while inner plate is made of zinc coated steel sheet. In the middle is high pressure foamed hard polyurethane as insulation.
2. Filter sections of Aluminum pre-filter, medium filter, bag type filter HC filter are available upon application requirement.
3. High efficiency Aluminum fin copper chilled, Direct Expansion Coil, with drain pan, Hot water and electric step heating; Steam and Electrode type Humidifier are available.
4. Energy saving Heat Wheel Recovery section are available.
5. Forward, Backward inclined and Aero Foil Fans are available for specific fan application; Fan assembly framework with adjustable motor base for proper fan belt tension adjustment; Spring isolator for Fan Assembly Frame is special non defective type for protection of vigorous transportation.
6. Low leakage air dampers for fresh air, return air and exhaust air adjustment.
7. BA control factory installed as option for saving installation time and labor cost.
Applications: Shopping Malls/Multiplexes/Small Offices
We are a highly reputable and reliable company in the manufacturing, supplying, and trading industry. Our focus is on providing top-quality materials and equipment to clients in the market. We have successfully introduced Ceiling Mounted Air Handling Units to our product range. These units are designed for both private and commercial use. Our primary objective is to meet our clients' requirements by offering them the most exclusive and high-quality materials available. Additionally, we aim to make these ceiling mounted air handling units affordable for our clients.
|
Data Sheet
RFPD/4H Series Return Air Condition (Z-TYPE,J-TYPE) | ||||||||||||||
Model RFPD/4H | Air Flow (m³/h) | Rated cooling cap. (KW) | Rated heating cap. (KW) | Water Flow (m³/h) | Water D.P. (kpa) | ESP (pa) | Motor power (KW) | Dimension | Weight (KG) | Noise dB(A) | Water pipe (DN) | Drain pipe (DN) | ||
L | W | H | ||||||||||||
010 | 1000 | 5.1 | 10.2 | 0.88 | 4.2 | 60 | 0.25 | 850 | 600 | 520 | 56 | 57 | 32 | 25 |
015 | 1500 | 8.4 | 15.2 | 1.44 | 9 | 60 | 0.25 | 950 | 650 | 570 | 63 | 57 | 40 | 25 |
020 | 2000 | 11.7 | 21.4 | 2.01 | 10.8 | 60 | 0.25 | 1100 | 750 | 570 | 81 | 58 | 40 | 25 |
025 | 2500 | 14.7 | 25.4 | 2.53 | 17.6 | 90 | 0.37 | 1100 | 850 | 570 | 83 | 59 | 40 | 25 |
030 | 3000 | 17.9 | 31.5 | 3.08 | 32 | 150 | 0.55 | 1100 | 1000 | 570 | 102 | 60 | 40 | 25 |
040 | 4000 | 23.6 | 41.1 | 4.06 | 60 | 180 | 0.75 | 1100 | 1280 | 620 | 106 | 60 | 40 | 25 |
050 | 5000 | 28.6 | 51.3 | 4.92 | 40 | 200 | 0.45x2 | 1100 | 1500 | 620 | 132 | 61 | 40 | 25 |
060 | 6000 | 35 | 62 | 6.02 | 42 | 200 | 0.55X2 | 1100 | 1630 | 620 | 152 | 62 | 50 | 25 |
070 | 7000 | 41 | 71 | 7.05 | 56 | 250 | 0.75x2 | 1100 | 1730 | 680 | 210 | 63 | 50 | 25 |
080 | 8000 | 45.5 | 84.3 | 7.83 | 32 | 250 | 0.75X2 | 1100 | 1730 | 740 | 251 | 63 | 50 | 25 |
090 | 9000 | 53 | 92.5 | 9.12 | 36 | 250 | 0.75x2 | 1100 | 1830 | 740 | 282 | 65 | 50 | 25 |
105 | 10500 | 62.1 | 110 | 10.68 | 48 | 280 | 1.1x2 | 1200 | 2130 | 740 | 302 | 67 | 50 | 25 |
120 | 12000 | 71 | 133 | 12.21 | 62 | 280 | 1.1x2 | 1200 | 2130 | 840 | 307 | 67 | 50 | 25 |
135 | 13500 | 77 | 148 | 13.24 | 25.4 | 320 | 1.8x2 | 1200 | 2130 | 900 | 375 | 69 | 65 | 25 |
150 | 15000 | 86.5 | 153.5 | 14.88 | 26.4 | 320 | 2.2x2 | 1200 | 2130 | 970 | 386 | 70 | 65 | 25 |
NOTE: 1. Cooling conditions: inlet air DB27°C,WB19.5°C, inlet water temperature 7°C/12°C. 2. Heating conditions: inlet air DB21°C, inlet water temperature 60°C/50°C. | ||||||||||||||
RFPD/4X Series Fresh Air Condition (Z TYPE;J TYPE) | ||||||||||||||
Model RFPD/4X | Air Flow (m³/h) | Rated cooling cap. (KW) | Rated heating cap. (KW) | Water Flow (m³/h) | Water D.P. (kpa) | ESP (pa) | Motor power (KW) | Dimension | Weight (KG) | Noise dB(A) | Water pipe (DN) | Drain pipe (DN) | ||
L | W | H | ||||||||||||
010 | 1000 | 14 | 13.5 | 2.41 | 16.3 | 60 | 0.25 | 850 | 600 | 520 | 56 | 57 | 32 | 25 |
015 | 1500 | 20.2 | 19.8 | 3.47 | 34 | 60 | 0.25 | 950 | 650 | 570 | 63 | 57 | 40 | 25 |
020 | 2000 | 27 | 26.6 | 6.64 | 45 | 60 | 0.25 | 1100 | 750 | 570 | 81 | 58 | 40 | 25 |
025 | 2500 | 31 | 31.6 | 5.33 | 26 | 90 | 0.37 | 1100 | 850 | 570 | 83 | 59 | 40 | 25 |
030 | 3000 | 40 | 41.8 | 6.88 | 47 | 150 | 0.55 | 1100 | 1000 | 570 | 102 | 60 | 40 | 25 |
040 | 4000 | 50 | 52 | 8.6 | 31 | 180 | 0.75 | 1100 | 1280 | 620 | 106 | 60 | 40 | 25 |
050 | 5000 | 65 | 64 | 11.18 | 63 | 200 | 0.45x2 | 1100 | 1500 | 620 | 132 | 61 | 40 | 25 |
060 | 6000 | 73 | 74.2 | 12.56 | 12 | 200 | 0.55x2 | 1100 | 1630 | 620 | 152 | 62 | 50 | 25 |
070 | 7000 | 84 | 85.5 | 14.45 | 16 | 250 | 0.75x2 | 1100 | 1730 | 680 | 210 | 63 | 50 | 25 |
080 | 8000 | 101 | 102.2 | 17.37 | 14.5 | 250 | 0.75X2 | 1100 | 1730 | 740 | 251 | 63 | 50 | 25 |
090 | 9000 | 113 | 114.2 | 19.44 | 18.6 | 250 | 0.75x2 | 1100 | 1830 | 740 | 282 | 65 | 50 | 25 |
105 | 10500 | 135 | 136 | 23.22 | 29 | 280 | 1.1X2 | 1200 | 2130 | 740 | 302 | 67 | 50 | 25 |
120 | 12000 | 151 | 154 | 25.97 | 19.6 | 280 | 1.1X2 | 1200 | 2130 | 840 | 307 | 67 | 50 | 25 |
135 | 13500 | 166 | 179 | 28.55 | 16.3 | 320 | 1.8X2 | 1200 | 2130 | 900 | 375 | 69 | 65 | 25 |
150 | 15000 | 185 | 202 | 31.82 | 18.2 | 320 | 2.2x2 | 1200 | 2130 | 970 | 386 | 70 | 65 | 25 |
NOTE: 1. Cooling conditions: inlet air DB27°C,WB19.5°C, inlet water temperature 7°C/12°C. 2. Heating conditions: inlet air DB21°C, inlet water temperature 60°C/50°C. | ||||||||||||||
|
Product Description
Features:
Customizable High Quality Commercial HVAC Ceiling Type Air Handling Unit for Shopping Mall/Multiplex/Small Office
1. Double 25mm and 50mm Skin Panel, outer plate is made of high quality steel sheet, while inner plate is made of zinc coated steel sheet. In the middle is high pressure foamed hard polyurethane as insulation.
2. Filter sections of Aluminum pre-filter, medium filter, bag type filter HC filter are available upon application requirement.
3. High efficiency Aluminum fin copper chilled, Direct Expansion Coil, with drain pan, Hot water and electric step heating; Steam and Electrode type Humidifier are available.
4. Energy saving Heat Wheel Recovery section are available.
5. Forward, Backward inclined and Aero Foil Fans are available for specific fan application; Fan assembly framework with adjustable motor base for proper fan belt tension adjustment; Spring isolator for Fan Assembly Frame is special non defective type for protection of vigorous transportation.
6. Low leakage air dampers for fresh air, return air and exhaust air adjustment.
7. BA control factory installed as option for saving installation time and labor cost.
Applications: Shopping Malls/Multiplexes/Small Offices
We are a highly reputable and reliable company in the manufacturing, supplying, and trading industry. Our focus is on providing top-quality materials and equipment to clients in the market. We have successfully introduced Ceiling Mounted Air Handling Units to our product range. These units are designed for both private and commercial use. Our primary objective is to meet our clients' requirements by offering them the most exclusive and high-quality materials available. Additionally, we aim to make these ceiling mounted air handling units affordable for our clients.
|
Data Sheet
RFPD/4H Series Return Air Condition (Z-TYPE,J-TYPE) | ||||||||||||||
Model RFPD/4H | Air Flow (m³/h) | Rated cooling cap. (KW) | Rated heating cap. (KW) | Water Flow (m³/h) | Water D.P. (kpa) | ESP (pa) | Motor power (KW) | Dimension | Weight (KG) | Noise dB(A) | Water pipe (DN) | Drain pipe (DN) | ||
L | W | H | ||||||||||||
010 | 1000 | 5.1 | 10.2 | 0.88 | 4.2 | 60 | 0.25 | 850 | 600 | 520 | 56 | 57 | 32 | 25 |
015 | 1500 | 8.4 | 15.2 | 1.44 | 9 | 60 | 0.25 | 950 | 650 | 570 | 63 | 57 | 40 | 25 |
020 | 2000 | 11.7 | 21.4 | 2.01 | 10.8 | 60 | 0.25 | 1100 | 750 | 570 | 81 | 58 | 40 | 25 |
025 | 2500 | 14.7 | 25.4 | 2.53 | 17.6 | 90 | 0.37 | 1100 | 850 | 570 | 83 | 59 | 40 | 25 |
030 | 3000 | 17.9 | 31.5 | 3.08 | 32 | 150 | 0.55 | 1100 | 1000 | 570 | 102 | 60 | 40 | 25 |
040 | 4000 | 23.6 | 41.1 | 4.06 | 60 | 180 | 0.75 | 1100 | 1280 | 620 | 106 | 60 | 40 | 25 |
050 | 5000 | 28.6 | 51.3 | 4.92 | 40 | 200 | 0.45x2 | 1100 | 1500 | 620 | 132 | 61 | 40 | 25 |
060 | 6000 | 35 | 62 | 6.02 | 42 | 200 | 0.55X2 | 1100 | 1630 | 620 | 152 | 62 | 50 | 25 |
070 | 7000 | 41 | 71 | 7.05 | 56 | 250 | 0.75x2 | 1100 | 1730 | 680 | 210 | 63 | 50 | 25 |
080 | 8000 | 45.5 | 84.3 | 7.83 | 32 | 250 | 0.75X2 | 1100 | 1730 | 740 | 251 | 63 | 50 | 25 |
090 | 9000 | 53 | 92.5 | 9.12 | 36 | 250 | 0.75x2 | 1100 | 1830 | 740 | 282 | 65 | 50 | 25 |
105 | 10500 | 62.1 | 110 | 10.68 | 48 | 280 | 1.1x2 | 1200 | 2130 | 740 | 302 | 67 | 50 | 25 |
120 | 12000 | 71 | 133 | 12.21 | 62 | 280 | 1.1x2 | 1200 | 2130 | 840 | 307 | 67 | 50 | 25 |
135 | 13500 | 77 | 148 | 13.24 | 25.4 | 320 | 1.8x2 | 1200 | 2130 | 900 | 375 | 69 | 65 | 25 |
150 | 15000 | 86.5 | 153.5 | 14.88 | 26.4 | 320 | 2.2x2 | 1200 | 2130 | 970 | 386 | 70 | 65 | 25 |
NOTE: 1. Cooling conditions: inlet air DB27°C,WB19.5°C, inlet water temperature 7°C/12°C. 2. Heating conditions: inlet air DB21°C, inlet water temperature 60°C/50°C. | ||||||||||||||
RFPD/4X Series Fresh Air Condition (Z TYPE;J TYPE) | ||||||||||||||
Model RFPD/4X | Air Flow (m³/h) | Rated cooling cap. (KW) | Rated heating cap. (KW) | Water Flow (m³/h) | Water D.P. (kpa) | ESP (pa) | Motor power (KW) | Dimension | Weight (KG) | Noise dB(A) | Water pipe (DN) | Drain pipe (DN) | ||
L | W | H | ||||||||||||
010 | 1000 | 14 | 13.5 | 2.41 | 16.3 | 60 | 0.25 | 850 | 600 | 520 | 56 | 57 | 32 | 25 |
015 | 1500 | 20.2 | 19.8 | 3.47 | 34 | 60 | 0.25 | 950 | 650 | 570 | 63 | 57 | 40 | 25 |
020 | 2000 | 27 | 26.6 | 6.64 | 45 | 60 | 0.25 | 1100 | 750 | 570 | 81 | 58 | 40 | 25 |
025 | 2500 | 31 | 31.6 | 5.33 | 26 | 90 | 0.37 | 1100 | 850 | 570 | 83 | 59 | 40 | 25 |
030 | 3000 | 40 | 41.8 | 6.88 | 47 | 150 | 0.55 | 1100 | 1000 | 570 | 102 | 60 | 40 | 25 |
040 | 4000 | 50 | 52 | 8.6 | 31 | 180 | 0.75 | 1100 | 1280 | 620 | 106 | 60 | 40 | 25 |
050 | 5000 | 65 | 64 | 11.18 | 63 | 200 | 0.45x2 | 1100 | 1500 | 620 | 132 | 61 | 40 | 25 |
060 | 6000 | 73 | 74.2 | 12.56 | 12 | 200 | 0.55x2 | 1100 | 1630 | 620 | 152 | 62 | 50 | 25 |
070 | 7000 | 84 | 85.5 | 14.45 | 16 | 250 | 0.75x2 | 1100 | 1730 | 680 | 210 | 63 | 50 | 25 |
080 | 8000 | 101 | 102.2 | 17.37 | 14.5 | 250 | 0.75X2 | 1100 | 1730 | 740 | 251 | 63 | 50 | 25 |
090 | 9000 | 113 | 114.2 | 19.44 | 18.6 | 250 | 0.75x2 | 1100 | 1830 | 740 | 282 | 65 | 50 | 25 |
105 | 10500 | 135 | 136 | 23.22 | 29 | 280 | 1.1X2 | 1200 | 2130 | 740 | 302 | 67 | 50 | 25 |
120 | 12000 | 151 | 154 | 25.97 | 19.6 | 280 | 1.1X2 | 1200 | 2130 | 840 | 307 | 67 | 50 | 25 |
135 | 13500 | 166 | 179 | 28.55 | 16.3 | 320 | 1.8X2 | 1200 | 2130 | 900 | 375 | 69 | 65 | 25 |
150 | 15000 | 185 | 202 | 31.82 | 18.2 | 320 | 2.2x2 | 1200 | 2130 | 970 | 386 | 70 | 65 | 25 |
NOTE: 1. Cooling conditions: inlet air DB27°C,WB19.5°C, inlet water temperature 7°C/12°C. 2. Heating conditions: inlet air DB21°C, inlet water temperature 60°C/50°C. | ||||||||||||||